Type code

E

LM

3

xxxH

xxx

Product series

Filter type
LM = motor filter

Phases
3 = 3 phases

Inductance
e.g. 30 = 3.0 mH

Rated current (partly rounded)
e.g. 004 = 4 A

Application range

Motor filters are applied to reduce the motor cable load and to decrease capacitive
discharge currents to PE in long motor cables.

A motor filter is required:
ƒ in very long motor cables (regardless of the compliance with EMC limit values).

Motor cables must comply with EMC limit values only with regard to conducted
interference emission.

ƒ When operating motors whose insulation systems are not suitable for inverter

operation. Lenze motors have insulations with greater thermal reserves.

Please note:
ƒ Operation is only permissible if a V/f or V/f

2

characteristic control and a switching

frequency of 8 ... 16 kHz is applied.
– The filter will overheat if it is operated at a switching frequency < 8 kHz.
– Ensure that the automatic switching frequency reduction is deactivated (see

documentation of the standard device).

ƒ The frequency inverter is loaded with an additional 12 per cent, approximately, of the

rated current of the motor filter.

ƒ The voltage drop at the motor filter averages 2−3 per cent of the max. output voltage

of the frequency inverter if the rated current of the motor filter and a frequency of 50
Hz is applied.

ƒ Overvoltages are supplied into the DC bus (+UG/−UG) via the motor filter. In this case,

the application of the motor filter in DC−bus operation is permissible.