3.1

L_8200Parameter − Initialisation of codes

Function library Lenze8200Drive.lib

Functions/function blocks

3−2

L

Lenze8200Drive.lib EN 1.0

3.1

L_8200Parameter − Initialisation of codes

Function block

With this FB you can parameterise up to 45 parameters (codes) in the frequency inverter.

The following parameterisation concepts are supported:

·

Parameterisation through direct instructions in the FBs

·

Parameterisation by means of codes ("online" parameterisation possible)

L_8200Parameter

abyFraction

anValue

byNoOfParameter

abySubCodeNo

awCodeNo

1

Code

SubCode

Fraction

Value

2

3

4

5

6

7

8

9

...

45

FB call in:

þ Cyclic task

(PLC_PRG)

þ Time−controlled task

(INTERVAL)

þ Event−controlled task

(EVENT)

o Interrupt task

Inputs

Data type

Information/possible settings

byNoOfParameter

Byte

Number of parameters to be transmitted (max. 45)

awCodeNo

Array of Word

Number of the code to be transmitted as parameter 1..45.

abySubCodeNo

Byte array

Number of the subcode to be transmitted as parameter 1..45.

abyFraction

Byte array

Number of decimal places for parameters 1..45

·

See also FB description L_ParWrite
in the Manual Function library LenzeDrive.lib.

anValue

Array of

integers

Value of the code to be transmitted as parameter 1..45.