Technical data
General data and operating conditions
l
40
EDKRBDRB47R DE/EN/FR 2.0
Environmental conditions
Climate
Storage
IEC/EN 60721−3−7 7K2 (−25 ... +55 °C)
Transport
7K2 (−25 ... +70 °C)
Operation
7K2 (−10 ... +55 °C)
Current derating at +45 ... +55 °C: 2.5 %/°C
Site altitude
0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of
5 %/1000 m
Pollution
EN 61800−5−1
Pollution degree 2
Vibration resistance
(9.81 m/s
2
= 1 g)
Transport
IEC/EN 60721−3−7 7M3
2 ... 9 Hz: amplitude 7.5 mm
9 ... 200 Hz: acceleration resistant up to 20 m/s
2
200 ... 500 Hz: acceleration resistant up to 40 m/s
2
Operation
IEC/EN 60721−3−3 3M8 stationary
2 ... 9 Hz: amplitude 15 mm
9 ... 200 Hz: acceleration resistant up to 50 m/s
2
IEC/EN 60721−3−7 7M3 mobile
2 ... 9 Hz: amplitude 7.5 mm
9 ... 200 Hz: acceleration resistant up to 20 m/s
2
200 ... 500 Hz: acceleration resistant up to 40 m/s
2
Mounting conditions
Mounting location
l
The mounting location must comply with the
device features mentioned in the chapter "General
data".
l
Flammable materials or substances may not be
placed in the vicinity of the brake resistor.
l
The heat generated by the brake resistor must be
dissipated freely.
Mounting position
Vertically suspended with connecting cables at the
bottom.
Free space
at the top
> 200 mm
at the bottom
> 100 mm
to the sides
> 25 mm