Technical data – Lenze ERBDxxxRxxxxRB User Manual

Page 40

Advertising
background image

Technical data

General data and operating conditions

4

l

40

EDKRBDRB47R DE/EN/FR 2.0

Environmental conditions

Climate

Storage

IEC/EN 60721−3−7 7K2 (−25 ... +55 °C)

Transport

7K2 (−25 ... +70 °C)

Operation

7K2 (−10 ... +55 °C)
Current derating at +45 ... +55 °C: 2.5 %/°C

Site altitude

0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of
5 %/1000 m

Pollution

EN 61800−5−1

Pollution degree 2

Vibration resistance

(9.81 m/s

2

= 1 g)

Transport

IEC/EN 60721−3−7 7M3

2 ... 9 Hz: amplitude 7.5 mm

9 ... 200 Hz: acceleration resistant up to 20 m/s

2

200 ... 500 Hz: acceleration resistant up to 40 m/s

2

Operation

IEC/EN 60721−3−3 3M8 stationary

2 ... 9 Hz: amplitude 15 mm

9 ... 200 Hz: acceleration resistant up to 50 m/s

2

IEC/EN 60721−3−7 7M3 mobile

2 ... 9 Hz: amplitude 7.5 mm

9 ... 200 Hz: acceleration resistant up to 20 m/s

2

200 ... 500 Hz: acceleration resistant up to 40 m/s

2

Mounting conditions

Mounting location

l

The mounting location must comply with the
device features mentioned in the chapter "General
data".

l

Flammable materials or substances may not be
placed in the vicinity of the brake resistor.

l

The heat generated by the brake resistor must be
dissipated freely.

Mounting position

Vertically suspended with connecting cables at the
bottom.

Free space

at the top

> 200 mm

at the bottom

> 100 mm

to the sides

> 25 mm

Advertising