Electrical installation, Stop – Lenze EPZ-10203 User Manual

Page 16

Advertising
background image

Electrical installation

Assignment of the terminals

EDK10203EZ3 DE/EN/FR 4.1

16

l

H1_E_INST−Ink−TTL_en

Terminal

Signal type

Function

Technical data

Remarks

X1/I15

Digital
inputs

LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Input current: max. 8
mA at 24 V

X1/I16

X1/O5
...
X1/O8

Digital
outputs

LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Load capacity: max.
1 A

X2/A

^

Reference potential for
analog signals

l

Use shielded
cables

l

Connect the
screen at both
ends

X2/AI4

Analog
inputs

Input voltage:
−10 V ... +10 V
Resolution:
10 bit + sign

X2/AI5

X2/+O24

DC voltage supply

18 VDC ... 30 VDC

Connected via
emergency off at the
Drive PLC

X2/

^

24

GND, reference potential
for digital outputs

X4/I9
...
X4/I14

Digital
inputs

LOW (0 V ... +4 V)
HIGH (+13 V ... +30 V)
Input current: max. 8
mA at 24 V

(

Stop!

ƒ

Ensure a sufficient dimensioning of the DC voltage supply, if the loads are
connected to the digital outputs.

ƒ

The extension board must exclusively be supplied separately.The internal
supply via the Drive PLC is not permissible.

Advertising