Technical data

Rated data

4

l

46

EDKRBD180R DE/EN/FR 7.0

4.2

Rated data

Electrical data

R

B

P

d

Q

B

U

max

[

W]

[W]

[kWs]

[V

DC

]

ERBD015R04K0

15

4000

547

900

ERBD018R01K6

18

1600

240

800

ERBD018R03K0

3000

375

ERBD018R06K0

6000

900

ERBD022R03K0

22

3000

375

ERBD033R02K0

33

2000

240

ERBD047R01K2

47

1200

174

ERBD068R800W

68

800

120

ERBD082R600W

82

600

87

ERBD100R600W

100

600

83

ERBD180R300W

180

300

45

R

B

Resistance

P

d

Permanent power

Q

B

Heat quantity

U

max

Max. operating voltage

Temperatures

T

nom

T

TK

T

max

[°C]

Inside

450

600

1000

At the housing

200

250

750

On the clearance
edge

*)

180

220

500

T

nom

Maximum temperature for rated data

T

TK

Temperature at which the thermal contact is activated

T

max

Maximum temperature in the case of improper use

*)

Measured for air as the ambient medium (small coefficient of thermal
conductivity); if materials which heat up are located at the clearance edge
(greater coefficient of thermal conductivity), the temperature continues to
rise.