Electrical installation

Wiring

6

EDK82ZAFSC DE/EN/FR 5.0

37

l

H2_verdrahtung−INS_Klemmenbeleg

Wiring

Terminal data

Range

Values

Electrical connection

Terminal strip with screw connection

Possible connections

rigid:

1.5 mm

2

(AWG 16)

flexible:

without wire end ferrule
1.0 mm

2

(AWG 18)

with wire end ferrule, without plastic sleeve
0.5 mm

2

(AWG 20)

with wire end ferrule, with plastic sleeve
0.5 mm

2

(AWG 20)

Tightening torque

0.22 ... 0.25 Nm (1.9 ... 2.2 lb−in)

Bare end

5 mm