2 Safety instructions

Residual hazards

EDK82ZZ113 DE/EN/FR 2.1

20

Restgefahren-UR_Warn

Residual hazards

Danger!

Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains

disconnection.
Possible consequences:

ƒ

Death or severe injuries when touching the power terminals.

Protective measures:

ƒ

Switch off the power supply and wait for at least three minutes before

working on the power terminals.

ƒ

Make sure that all power terminals are deenergised.

Danger!

Dangerous voltage
With the filter variants 200 and 210, the leakage current to earth (PE) is

> 3.5 mA AC or > 10 mA DC.
Possible consequences:

ƒ

Death or severe injuries when touching the device in case of a fault.

Protective measures:

ƒ

Take the measures specified in EN 61800-5-1. In particular:

– Fixed installation

– PE connection according to standard (PE conductor diameter ≥ 10 mm

2

or connect PE conductor twice)

Stop!

No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:

ƒ

Destruction of the device if the mains voltage is too high.

Protective measures:

ƒ

Observe the maximally permissible mains voltage.

ƒ

Fuse the device correctly on the supply side against mains fluctuations and

voltage peaks.

Warnings!

Conditions of acceptability:

ƒ

The E82ZZ filters must be mounted into an enclosure providing adequate

spacings.

ƒ

The terminals have not been evaluated for field wiring connection.

ƒ

These devices are only intended for use with Lenze 8200 vector inverters

with a controlled overvoltage means.