Technical data

General data and operating conditions

3

EDK82ZZ113 DE/EN/FR 2.1

21

H1_Daten-TD_Montagebed_E82ZZ

3

Technical data

General data and operating conditions

Standards

Approval

UL

UL 508C, Component Power Conversion Equipment -

Accessories (file no. E132659) for the US and Canada

Mains data

Mains types

With grounded neutral (TT /TN systems)

Operation permitted without restrictions

IT systems

230 V

Observe instructions for special measures in the

documentation for the basic device!

400 V

Max. mains voltage 400 V!

Observe instructions for special measures in the

documentation for the basic device!

Protection

Type of protection

EN 60529

IP 20

Not in the wire range of

the terminals

NEMA 250

Protection against contact to

type 1

Insulation resistance

EN 61800-5-1

Overvoltage category III

> 2000 m: Overvoltage category II

Leakage current

EN 61800-5-1

E82ZZ...B200

E82ZZ...B210

> 3.5 mA

Observe regulations and

safety instructions!

E82ZZ...B220

< 3.5 mA

Ambient conditions

Temperature

Storage

-25 ... +60 °C

Transport

-25 ... +70 °C

Operation

-10 ... +55 °C

Current derating from +40 to +55 °C: 2.5 %/°C

Site altitude

0 ... 4000 m amsl

1000 ... 4000 m amsl: Current derating by 5 %/1000 m

Pollution

EN 61800-5-1

Pollution degree 2

Vibration resistance

EN 50178, IEC 61800-5-1,

Germanischer Lloyd,

general conditions

Acceleration-resistant up to 0.7 g

Mounting conditions

Mounting location

In the control cabinet

Position

Standard: between mounting plate and basic device

Variant: to the left of the basic device

Mounting position

Vertical, connections on top