7

RG-MCMET

N2 Points

4.1 Metasys N2 Point Map

Table 3: Metasys N2 Point Map for MC3000 Series Drives

Point

Type

1

Point

#

Description (Point Name)

Read (R)/

Override (R/O)

Point
Units

Decimal

Places

MIN

Value

MAX

Value

Default

Value

1

1

Parameter Version

R

--

0

--

--

143

2

1

2

Software Version

R

--

0

--

--

043

2

1

3

Software Revision

R

--

0

--

--

05

2

1

4

Drive Config/Size

R

--

0

0

57

--

1

5

Drive Class

R

--

0

--

--

65

1

6

Total Runtime (RUNTIME HRS)

R

hrs

0

0

--

1

7

Total Runtime (RUNTIME MIN)

R

min

0

0

--

1

8

Operational Status (RUN STATUS)

R

--

0

0

10

--

1

9

Load Percent (LOAD PERCENT)

R

%

0

150

180

180

1

10

Motor Voltage (MOTOR VOLTS)

R

VAC

0

1

11

Present Fault (FAULT)

R

--

0

0

23

0

1

12

Recorded Fault 1

R

--

0

0

23

0

1

13

Recorded Fault 2

R

--

0

0

23

0

1

14

Recorded Fault 3

R

--

0

0

23

0

1

15

Recorded Fault 4

R

--

0

0

23

0

1

16

Recorded Fault 5

R

--

0

0

23

0

1

17

Recorded Fault 6

R

--

0

0

23

0

1

18

Recorded Fault 7

R

--

0

0

23

0

1

19

Recorded Fault 8

R

--

0

0

23

0

1

20

PID Feedback (PID FEEDBACK)

R

PID

0

Note 3

Note 3

Note 3

1

21

PID Setpoint Command (PID SETPOINT)

R

PID

0

Note 3

Note 3

Note 3

1

22

Actual Speed (ACTUAL FREQ)

R

Hz

2

0

12000

--

2

01

Fault Condition (OK.FAULT)

R

--

0

OK

FLT

OK

3

01

Command Speed (COMMAND SPD)

R/O

Hz

2

0

120.00

20.00

3

02

Keypad Command Speed (CMD KEY SPD)

R/O

Hz

2

0

120.00

20.00

3

03

Normal Acceleration (ACCEL)

R/O

sec

1

*

3600.0

30.0

3

04

Normal Deceleration (DECEL)

R/O

sec

1

*

3600.0

30.0

3

05

Local PID Command

R/O

PID

0

Note 3

Note 3

Note 3

3

06

Control Mode

R/O

--

0

4

01

History

R/O

--

0

0 (maintain)

1 (clear)

0

4

02

Start/Stop Drive (CMD RUN.STOP)

R/O

--

0

0 (stop)

1 (start)

0

4

03

Speed Control Auto/Manual

R/O

--

0

0 (auto)

1 (manual)

0

4

04

Clear Present Fault (CLEAR FAULT)

R/O

--

0

0

1 (clear)

NOTES:
1. Point Types: 1 = Analog Input; 2 = Binary Input; 3 = Analog Output; 4 = Binary Output

2. Current Value of the parameter version, software version and software revision.

3. Units, MIN/MAX Values: for this point are defined via Drive Parameters #31, 75 and 76 respectively.

Refer to notes in sections 4.2 and 4.4.

* Refer to MC3000 Installation & Operation Manual (M301)