N2 points – Lenze MC3000 Series Drives User Manual

Page 12

Advertising
background image

9

RG-MCMET

N2 Points

Point

Description

1-05:

Drive Class

This point represents the MC series drive class = 65 (41h).

1-06:

Total Runtime Hours

This point represents the total accumulated time the drive has run in hours. This value can
be reset to 0 by entering the password 4425 and restoring factory defaults via parameter
65 (PROGRAM).

1-07:

Total Runtime Minutes

This point represents the total accumulated time the drive has run in minutes. This
value can be reset to 0 by entering the password 4425 and restoring factory defaults via
parameter 65 (PROGRAM).

1-08:

Operational Status

This point is for monitoring the actual operating condition of the drive. The value returned
is a number between 0 and 10 which corresponds to one of the following operating states:

Value

Operational State

Value

Operational State

0

FAULT LOCKOUT

6

RUN

1

FAULT

7

ACCEL

2

START PENDING

8

DECEL

3

STOP

9

CURRENT LIMIT

4

DC BRAKE

10

DECEL OVERRIDE

5

RUN AT 0Hz

1-09:

Load %

This point represents the drive load as a percentage of full load. The high limit for this point
is dictated by Parameter 1 (Current Limit). Depending on the setting of Parameter 0 (Line
Volts), the drive is capable of delivering 150% or 180% of its rated output current. This
value can be viewed on the local display by pressing the Enter key once.

1-10:

Motor Voltage

This point represents the AC voltage that is currently being sent to the motor. This number
can be viewed on the local display by pressing the Enter key twice.