MA_p500 DE/EN/FR/ES/IT 2.0

2

UL_Warn_p500-M-Install_WiHis_p500

Approval
Underwriter Laboratories (UL), UL508 and CSA C22.2 No. 142-M1987, (UL File Number

E236341)

Ratings
ƒ Input 24 V DC, max. 1.7 A
ƒ Max. Surrounding temperature:

– P500 7: 55 °C, in vertical (landscape or portrait) mounting position only at relative

humidity of 60%rh with a linear derating to 30°C at 90%rh.

– P500 10,4: 55°C in vertical (landscape or portrait)mounting position only at a

relative humidity of 55%rh with a linear derating to 40°C at 90%rh.

– P500 15,0: 55°C in vertical (landscape or portrait)mounting position only at a

relative humidity of 45%rh with a linear derating to 40°C at 90%rh.

ƒ These devices are intended for mounting in the outer surface of an enclosure, Type 1,

4 and 4X indoor use only.

Warnings!

Field Wiring Markings
Wiring Terminal MSTB 2,5/3-STF-5,08:

ƒ

Use 60° or 60/75° C copper wire only.

ƒ

AWG 18 ... AWG 12 (0.82 mm

2

... 3.3 mm

2

)

ƒ

Torque 5...7 lb-in (0.5 ... 0.6 Nm)

Device

ƒ

For use in a pollution degree 2 and controlled environment only.

ƒ

For use on a Flat Surface of a Type 1, 4 and 4x Indoor Use Only Enclosure

Optional filed bus module

ƒ

Use only together with appropriate cable connectors, provided with screws

for securement and secure connector to avoid loosening.