Troubleshooting and fault elimination

Error messages

10

l

EDK82MVXXX EN 1.0

3.2

LEDs at the controller (operating status display)

LED

Operating status

green

red

on

off

Controller enabled

on

on

Mains switched on and automatic start inhibited

blinking

off

Controller inhibited

off

blinking every second

Fault active, check under C0161

off

blinking every 0.4 seconds

Undervoltage switch-off

fast blinking off

Motor parameter identification

3.3

Fault messages at the keypad or in the parameter setting
program Global Drive Control

Display

Fault

Cause

Remedy

Keypad PC

1)

noer

0

No fault

-

-

ccr

71

System fault

Strong interferences on control cables

Shield control cables

ccr

a

y

Ground or earth loops in the wiring

ce0

a

61

Communication error to AIF

Transmission of control commands via AIF is

interfered

Plug the communication module firmly into the hand

terminal

ce1

a

62

Communciation error at

CAN-IN1 with sync control

CAN-IN1 object receives faulty data or

communication interrupted

Plug-in connection for bus module

ó Check FIF

Check transmitter

Increase monitoring time under C0357/1 if necessary

ce2

a

63

Communication error to

CAN-IN2

CAN-IN2 object receives faulty data or

communication is interrupted

Plug-in connection for bus module

ó Check FIF

Check transmitter

Increase monitoring time under C0357/2 if necessary

ce3

a

64

Communication error to

CAN-IN1 with event or time

control

CAN-IN1 object receives faulty data or

communication interrupted

Plug-in connection for bus module

ó Check FIF

Check transmitter

Increase monitoring time under C0357/3 if necessary

ce4

a

65

BUS-OFF
(many communication errors

occurred)

Controller has received too many faulty telegrams

via system bus and has been disconnected from the

bus

Check whether the bus terminator is available

Check screen contact of the cables

Check PE connection

Check the bus load, if necessary, reduce the baud rate

ce5

a

66

CAN Time-Out

With remote parameter setting via system bus

(C0370):
Slave does not respond. Communication monitoring

time exceeded

Check wiring of the system bus

Check system bus configuration

Operation with module on FIF:
Internal error

Contact Lenze

ce6

a

67

Function module system bus

(CAN) is set to ”Warning” or

”BUS-OFF”
(only generated if C0128 = 1)

CAN controller sends ”Warning” or ”BUS-OFF”

Check whether the bus is terminated

Check screen contact of the cables

Check PE connection

Check the bus load, if necessary, reduce the baud rate

EEr

a

91

External error (TRIP-SET)

A digital signal used for the function TRIP set has

been activated.

Check external encoder

H05

a

105 Internal fault

Contact Lenze

id1

a

140 Faulty parameter identification Motor not connected

Connect motor

LP1

a

32

Error in motor phase
(only generated if C0597 = 1)

Failure of one/several motor phase(s)

Motor current too low

Check motor cables

V

min

boost

C

t

t

ith

di

d t

LP1

182 Error in motor phase

(only generated if C0597 = 2)

min

Connect motor with corresponding power or adapt

motor under C0599

LU

1030 DC-bus undervoltage

Mains voltage too low

Check mains voltage

LU

c

g

DC-bus voltage too low

Check supply module

400 V controller connected to 240 V mains

Connect the controller to the appropriate mains voltage