Parameter setting, Parameter setting using the keypad, 2 the menu – Lenze EDK82MVXXX User Manual

Page 7: The 10 most important drive parameters

Advertising
background image

Parameter setting

Parameter setting using the keypad

7

l

EDK82MVXXX EN 1.0

2.1.2

The menu

UUUUsssseeeerrrr

- The 10 most important drive parameters

After mains switching or plugging in the keypad during operation, the 10 codes defined to be the
most important in the user menu

User

(Code C0517) are available immediately.

In default setting the menu contains

User

all codes required for a standard application with linear V/f

characteristic control.

Code

Name

Lenze setting

C0050 Output frequency

Display: Output frequency without slip compensation

C0034 Setpoint selection range

-0-

Standard I/O

X3/8:

0 ... 5 V / 0 ... 10 V / 0 ... 20 mA

C0034 Setpoint selection range

0

Application I/O

X3/1U: 0 ... 5 V / 0 ... 10 V
X3/2U: 0 ... 5 V / 0 ... 10 V

C0007 Fixed configuration of digital inputs

-0-

E4

E3

E2

E1

C0007 Fixed configuration of digital inputs

0

CW/CCW

DCB

JOG2/3

JOG1/3

CW/CCW rotation

DC-injection brake

Selection of fixed setpoints

C0010 Minimum output frequency

0.00 Hz

C0011 Maximum output frequency

50.00 Hz

C0012 Acceleration time main setpoint

5.00 sec

C0013 Deceleration time main setpoint

5.00 sec

C0015 V/f rated frequency

50.00 Hz

C0016 U

min

boost

depending on the inverter type

C0002 Parameter set transfer/reset

see code table

Tip!

Use C0002 ” Parameter set transfer” to easily transfer configurations from one controller to the other
or to reset the controller to Lenze settings.