Connection data, Mounting steps, 4electrical installation – Lenze E82ZM11334B User Manual

Page 38

Advertising
background image

4

Electrical installation

Connection data

EDK82ZM113−002 DE/EN/FR 2.1

38

l

H1_E_INST−−−−(DUMMYSEITEVOR)−−−

Connection data

[mm

2

]

[AWG]

[mm]

[Nm]

[

lb−in]

E82ZM75134B

0.2 ... 4

0.25 ... 4

0.25 ... 2.5

24 ... 10

8

0.6 ... 0.8

5.3 ... 7.0

E82ZM22234B020

E82ZM40234B

0.2 ... 10

10

1.2 ... 2.0

10.6 ... 17.7

E82ZM75234B

E82ZM11334B

Mounting steps

How to connect the filter:
1. De−energise the control cabinet and fuse it against re−energisation.
2. Wait for at least 3 minutes before checking the standard device for isolation from

supply.

3. Wire the filter input cables and the filter output cables according to the connection

plan.
– Motor cable length < 100 m: shielded, low−capacitance (connect the shield with a

surface as large as possible on the mounting plate)
Motor cable length < 200 m: unshielded

– Observe tightening torque.

4. Wire the DC−bus cables (+UG/−UG) according to the connection plan.

– The terminals +UG und −UG must be connected using the same cable cross−section

as in the motor cable.

– Observe tightening torque.

)

Note!

When commissioning, please observe that operation is only permissible

ƒ

with V/f or V/f

2

characteristic control

ƒ

at a switching frequency of 2 ... 16 kHz