Electrical installation
Connection data
EDK82ZM113−002 DE/EN/FR 2.1
38
l
H1_E_INST−−−−(DUMMYSEITEVOR)−−−
Connection data
[mm
2
]
[AWG]
[mm]
[Nm]
[
lb−in]
E82ZM75134B
0.2 ... 4
0.25 ... 4
0.25 ... 2.5
24 ... 10
8
0.6 ... 0.8
5.3 ... 7.0
E82ZM22234B020
E82ZM40234B
0.2 ... 10
10
1.2 ... 2.0
10.6 ... 17.7
E82ZM75234B
E82ZM11334B
Mounting steps
How to connect the filter:
1. De−energise the control cabinet and fuse it against re−energisation.
2. Wait for at least 3 minutes before checking the standard device for isolation from
supply.
3. Wire the filter input cables and the filter output cables according to the connection
plan.
– Motor cable length < 100 m: shielded, low−capacitance (connect the shield with a
surface as large as possible on the mounting plate)
Motor cable length < 200 m: unshielded
– Observe tightening torque.
4. Wire the DC−bus cables (+UG/−UG) according to the connection plan.
– The terminals +UG und −UG must be connected using the same cable cross−section
as in the motor cable.
– Observe tightening torque.
)
Note!
When commissioning, please observe that operation is only permissible
ƒ
with V/f or V/f
2
characteristic control
ƒ
at a switching frequency of 2 ... 16 kHz