Residual hazards – Lenze ELM3−004H055 User Manual

Page 25

Advertising
background image

Safety instructions

Residual hazards

1

EDKLM3−XXX−001 DE/EN/FR 1.1

25

l

H1sic_EN−Hi_festinst

Application notes

Pictograph and signal word

Meaning

)

Note!

Important note to ensure troublefree operation

I

Tip!

Useful tip for simple handling

,

Reference to another documentation

Residual hazards

{

Danger!

Dangerous voltage

All power connections carry dangerous voltages both if the motor is at
standstill and after up to 3 minutes after mains switch off.

Possible consequences:

ƒ

Death or severe injuries after touching the power connections.

Protective measures:

ƒ

Wait for at least 3 minutes before working on the power connections.

ƒ

Check whether all power connections are de−energised.

{

Danger!

Dangerous voltage

The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.

Possible consequences:

ƒ

Death or severe injuries when the device is touched in the event of a fault.

Protective measures:

ƒ

Implement the actions required in the EN 61800−5−1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor diameter

³ 10 mm

2

or PE conductor must be connected twice)

Advertising
This manual is related to the following products: