Reducing the Fluid Temperature

512.14 Hydraulic Power Unit

Operation

23

Adjusting the Water Flow

On water-cooled heat exchangers, the water control valve regulates the flow of
water through the exchanger. MTS sets this valve to keep the hydraulic fluid
temperature between 64 and 68ºC (147 and 155ºF).

An out-of-adjustment water control valve can cause rapid overheating.

Check the Heat Exchanger

Changes in your water supply’s temperature may require adjustment of this
valve.

1. Start with the hydraulic fluid at room temperature. Make sure the heat

exchanger’s water supply valves are open.

2. Turn the start switch to LOW PRESS. Then turn the switch to HIGH

PRESS.

Put the HPU into a no-flow condition (where no fluid is flowing to other
hydraulic equipment).

3. Run the HPU for approximately 15 minutes to stabilize the temperature.

Check the fluid temperature in the sight glass.

If the temperature is between 64 and 68ºC (147 and 155ºF), stop.

If the temperature is
outside the operating
temperature range, turn
the valve’s screw to raise
or lower the water
temperature and repeat
this step. (Do not turn the
valve screw more than 1/2
turn at a time).

–Adjust the valve screw clockwise to decrease the reservoir

temperature.

–Adjust the valve screw counterclockwise to increase the reservoir

temperature.

Water Valve

1/2 Turn Maximum

Increase

Decrease