MTS Multi-Pump Control Manager User Manual

Page 29

Advertising
background image

Status Screen

Multi-Pump Control Manager

Operation

29

8

Status

Indicator: Indicates the state of the associated module.

Status - gray: Label.

Not Present - light gray: Indicates the module is not present.

Ready- green: Indicates the module is present but is not enabled.

Enabled - green: Indicates the module is enabled and is ready to
into a run condition (replaces READY).

Running Low- green: Indicates the associated pump module is
running in low pressure.

High Pressure - green: Indicates the associated pump module is
running in high pressure.

Overload - red: Indicates an overload condition exists and a fault
is active for the associated module

Sequence - red: Indicates that the PLC commanded the motor
contactor to close, but the contactor did not close after a 10 second
time period and a fault is active.

9

Hours

Indicator: Indicates the running time in hours of the associated
module.

Hours - gray: Label.

Value - gray: The number of total hours the associated module has
been running.

10

Mute

Pushbutton: Allow you to mute the light buzzer if a fault or alarm
activates.

11

Stop Relay Indicator

Indicates whether the MPCM's safety relay is tripped.
E-Stop Relay - gray - OK: indicates the MPCM's safety relay has
not tripped.

E-Stop Relay - red - Fault: Indicates that the MPCM's safety relay
has tripped.
The cause of a safety relay trip is either an External E-Stop
Button, an HPU E-Stop Button, or an HPU Watchdog timer.

12

HMI E-Stop Indicator

Indicates whether the HMI E-Stop Button has been pressed.

HMI E-Stop - gray - OK: Indicates that the HMI E-Stop button has
not been pressed and is in the reset (closed) state.

HMI E-Stop - red - Fault: Indicates that the HMI E-Stop Button
has been pressed and is in the open state.

13

External E-Stops
Pushbutton Indicator

Indicates whether an external E-Stop chain has been pressed. User
defined text.

Text - gray - OK: Specific external e-stop chain does not have a
button that has been pressed and is in the reset (closed state).

Text - red - Fault: Indicates that the specific external e-stop chain
has an e-stop button that has been pressed, and is in the open state.

Item Name

Description

Advertising