PAGE 26 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)

Figure 12. Connecting Loads

Connecting Loads

Loads can be connected to the generator by using the

Output

Terminal Lugs or the convienience receptacles
(See Figure 12). Make sure to read the operation manual
before attempting to connect a load to the generator.

To protect the

Output Terminal Lugs from overload, a

3-pole, 110 amp,

main

circuit breaker is provided. Make sure to

switch

ALL

circuit breakers to the OFF position prior to starting

the engine.

DCA-45USI — OUTPUT TERMINAL PANEL FAMILIARIZATION

Over Current Relay

An

over current relay (Figure 13) is connected to the main

circuit breaker. In the event of an overload, both the circuit
breaker and the over current relay may trip. If the circuit
breaker can not be reset, the

reset button on the over cur-

rent relay must be pressed. The over current relay is lo-
cated in the control box.

Figure 13. Over Current Relay

Blower Fan

This unit has an intake fan located at the rear of the machine
to draw outside air into the cabinet to cool the engine. The
fan has a 10 amp AC fuse located beneath the

Voltage

Selector Switch (Figure 14).

This fuse has current running through it any
time the engine is operating. THIS FUSE
IS NOT
connected to the main circuit
breaker OF the generator. Attempting to

replace the fuse with the engine
and/or generator operating could
result in

electrocution and severe

bodily harm. ALWAYS turn the
unit completely off before
attempting to replace or handle
THIS fuse

DANGER:

Figure 14. Blower Fan Fuse