Figure 21. Voltage Selector Switch 240/139V

Three-Phase Position

DCA-45USI — OUTPUT TERMINAL PANEL CONNECTIONS

UVWO Terminal Output Voltages

Various output voltages can be obtained using the using the
Output Terminal Lugs. The voltages at the terminals are
dependent on the position of the

Voltage Selector Switch

and the adjustment of the

Voltage Regulator Control Knob.

Remember the voltage selector switch determines the

range

of the output voltage. The voltage regulator (VR) allows the
user to increase or decrease the selected voltage.

3Ø 240/139 Output Terminal Lug Voltages

1. Place the voltage selector switch in the 3Ø 240/139

position as shown in Figure 21.

Figure 22. Output Terminal Lugs

240/139V Three Phase Connections

2. Connect the load wires to the

Output Terminal Lugs as

shown in Figure 22.

3. Turn the voltage regulator knob (Figure 23) clockwise to

increase voltage output, turn counterclockwise to
decrease voltage output.

3Ø 208V/1Ø120V Output Terminal Lug Voltages

1. Place the voltage selector switch in the 3Ø 240/139

position as shown in Figure 24.

Figure 23. Voltage Regulator Knob

Use this position for
3Ø-208 or 1Ø120V.

2. Connect the load wires to the

Output Terminal Lugs as

shown in Figure 25.

3. Turn the voltage regulator knob (Figure 23) clockwise to

increase voltage output, turn counterclockwise to
decrease voltage output.

NOTE

To achieve a 3Ø 208V output,
the voltage selector switch
must be in the 3Ø 240/139V
position and the voltage
regulator must be adjusted to
208V.

Figure 25

.

Output Terminal Lugs

3Ø-208V/120V Connections

Figure 24. Voltage Selector
Switch 3Ø-208V/1Ø-120V