PAGE 36 — DCA-45USI — OPERATION AND PARTS MANUAL (STD) — REV. #2 (04/22/05)

5. Preheat the engine

glow plugs by turning the ignition

key (Figure 42) to the PRE-HEAT/RUN position. When
the preheat lamp (Figure 43) turns off, proceed
to step 6.

Figure 43. Pre-Heat Indicator Lamp

WARNING:

WARNING:

WARNING:

WARNING:

WARNING:

The engine's exhaust contains harmful

emissions.

ALWAYS have adequate

ventilation when operating. Direct exhaust
away from nearby personnel.

DCA-45USI — GENERATOR START-UP PROCEDURE

Figure 39. Load Connections

NEVER! manually start the engine with the
main, GFCI or auxiliary circuit breakers in
the ON (closed) position.

CAUTION:

1. Be sure and place the

main, G.F.C.I. and aux. circuit

breakers (Figure 40) in the OFF position prior to starting
the engine.

Before Starting

Figure 38. Main, Aux. and GFCI

Circuit Breakers

2. Connect the load to the

Output Terminal Lugs or

auxiliary receptacles as shown in Figure 39. These load
connection points can be found on the output terminal
panel.

3. Close all engine enclosure doors (Figure 40).

Figure 40. Engine Enclosure Doors

4. Place the voltage selector switch in the desired voltage

position (Figure 41).

Figure 41. Voltage Selector Switch

Figure 42. Ignition Switch

(Pre-Heat/Run Position)