PAGE 18 — DCA45SSIU3 50 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (12/19/08)

GENERATOR CONTROL PANEL

Generator Control Panel

Figure 4.

The defi nitions below describe the controls and functions
of the DCA45SSIU3 Generator Control Panel (Figure 4).

Main Circuit Breaker

1.

—This three-pole, 110A main

breaker is provided to protect the the U,V, and W
Output Terminal Lugs from overload.

Voltage Regulator Control

2.

— Allows ±15% manual

adjustment of the generator’s output voltage.

Frequency Meter

3.

— Indicates the output frequency

in hertz (Hz). Normally 50 Hz.

AC Ammeter

4.

— Indicates the amount of current the

load is drawing from the generator per leg selected
by the ammeter phase-selector switch.

AC Voltmeter

5.

— Indicates the output voltage present

at the U,V, and W Output Terminal Lugs.

Ammeter Change-Over Switch

6.

— This switch allows

the AC ammeter to indicate the current fl owing to the
load connected to any phase of the output terminals,
or to be switched off. This switch does not effect the
generator output in any fashion, it is for current reading
only.

Voltmeter Change-Over Switch

7.

— This switch allows

the AC voltmeter to indicate phase to phase voltage
between any two phases of the output terminals or to
be switched off.

Located behind the generator control panel is the Generator
Control Box. This box contains some of the necessary
electronic components required to make the generator
function.

The Control Box is equipped with the following major
components:

Over-Current Relay

Automatic Voltage Regulator (AVR)

Starter Relay

Current Transformer

Voltage Selector Switch

Main Circuit Breaker

NOTICE

Remember the overcurrent relay monitors the current
fl owing from the U,V, and W Output Terminal Lugs
to the load.

In the event of a short circuit or over current condition,
it will automatically trip the 110 amp main breaker.

To restore power to the Output Terminal Panel, press
the reset button on the overcurrent relay and place the
main circuit breaker in the closed position (ON).