PAGE 34 — DCA45SSIU3 50 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (12/19/08)

GENERATOR START-UP PROCEDURE

BEFORE STARTING

Place the

1.

main, G.F.C.I., and aux. circuit breakers (Figure

35) in the OFF position prior to starting the engine.

Main, Aux. and GFCI

Figure 35.

Circuit Breakers (OFF)

Make sure the

2.

voltage change-over board has been

confi gured for the desired output voltage.

Connect the load to the

3.

receptacles or the output

terminal lugs as shown in Figure 10. These load
connection points can be found on the output terminal
panel and the output terminal panel’s hard wire hookup
panel.

Tighten terminal nuts securely to prevent load wires

4.

from slipping out.

Close all engine enclosure doors (Figure 36).

5.

Engine Enclosure Doors

Figure 36.

CAUTION

The engine’s exhaust contains harmful emissions.
ALWAYS have adequate ventilation when operating.
Direct exhaust away from nearby personnel.

WARNING

NEVER manually start the engine with the main, GFCI or
auxiliary
circuit breakers in the ON (closed) position.

INCORRECT

CORRECT

STARTING

Place the

1.

voltage selector switch in the desired

voltage position (Figure 37)..

Voltage Selector Switch

Figure 37.

Preheat the engine glow plugs by turning the ignition

2.

key (Figure 38) to the “OPERATION” position.

Ignition Switch

Figure 38.

(Operation/PreHeat Position)

When the preheat lamp illuminates (Figure 39), turn the

3.

ignition key to the “start” position. Once the engine
starts, release the ignition key and allow it to return to
the “operation” position (Figure 38).

Pre-Heat Lamp

Figure 39.

Let the engine run for 3-5 minutes, listen and check

4.

for any abnormal sounds or smells. Check for fuel
leaks, and noises that would associate with a loose
cover or hardware. If any of the above mentioned
conditions exists, shut-down the engine and correct
the problem.