DCA45SSIU3 50 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #2 (12/19/08) — PAGE 47

TROUBLESHOOTING (GENERATOR)

Practically all breakdowns can be prevented by proper handling and maintenance inspections, but in the event of a
breakdown, use Table 17 shown below for diagnosis of the Generator. If the problem cannot be remedied, consult our
company’s business offi ce or service plant.

Generator Troubleshooting

Table 17.

Symptom

Possible Problem

Solution

No Voltage Output

AC Voltmeter defective?

Check output voltage using a voltmeter.

Is wiring connection loose?

Check wiring and repair.

Is AVR defective?

Replace if necessary.

Defective Rotating Rectifi er?

Check and replace.

Defective Exciter Field?

Check for approximately 17.3 ohms across J & K on CN1

Low Voltage Output

Is engine speed correct?

Turn engine throttle lever to “High”.

Is wiring connections loose?

Check wiring and repair.

Defective AVR?

Replace if necessary.

High Voltage Output

Is wiring connections loose?

Check wiring and repair.

Defective AVR?

Replace if necessary.

Circuit Breaker Tripped

Short Circuit in load?

Check load and repair.

Over current?

Confi rm load requirements and reduce.

Defective circuit breaker?

Check and replace.

Over current Relay actuated?

Confi rm load requirement and replace.