Han- yellock, Modules, Modules features – Northern Connectors Harting Han-Yellock Industrial Connectors User Manual

Page 22: Technical characteristics

Advertising
background image

25

.

22

Han-

Yellock

Han-Yellock

®

Modules

Features

• Snap-in assembly from mating side and from termination side

• Bus bar within bridge attachements

• Finger safe design

• Fast and tool-less assembly

• Wiring with male contacts only
Placement for Han-Yellock

®

30

with 3 Han-Yellock

®

modules

Placement for Han-Yellock

®

60

with 6 Han-Yellock

®

modules

Current carrying capacity

The current carrying capacity of the connectors is limited by the

thermal load capability of the contact element material including

the connections and the insulating parts. The derating curve

is therefore valid for currents which flow constantly (non-inter-

mittent) through each contact element of the connector evenly,

without exceeding the allowed maximum temperature.

Measuring and testing techniques according to

DIN EN 60 512-5-2

Operating current

Ambient temperature

➀ wire gauge: 1.5 mm²
➁ wire gauge: 2.5 mm²
➂ wire gauge: 4 mm²

for connector with 3 Han-Yellock

®

modules, fully loaded

(multiplier 1:1)

Technical characteristics

Specifications

DIN EN 60 664-1

DIN EN 61 984

Modules

Electrical data

acc. to EN 61 984

20 A 500 V 6 kV 3

Rated current

20 A

Rated voltage

500 V

Rated impulse voltage

6 kV

Pollution degree

3

Pollution degree 2 also

20 A 690 V 8 kV 2

Insulation resistance

≥ 10

10

Ω

Material

PC

Limiting temperatures

-40 °C ... +125 °C

Flammability acc. to UL 94

V 0

Mechanical working life

- mating cycles

≥500

Contacts

Material

copper alloy

Surface

- hard-silver plated

3 µm Ag

- hard-gold plated

2 µm Au over 3 µm Ni

Contact resistance

≤ 2 mΩ

Crimp terminal

- Wire gauge

0.14 ... 4 mm²

- AWG

26 ... 12

Stripping length

6.5 mm

Tools

see chapter 99

Advertising