RKI Instruments 35-3000RKA-LEL User Manual

Page 4

Advertising
background image

4 • Sample Draw Combustible Gas Detector

Status lights

Two status lights are above the flowmeter. They are also visible through the window in
the housing door.

Pilot light

The green Pilot light is on when the sample draw detector is receiving power.

Fail light

The red Fail light is on when the sample flow rate is below the low flow level.

NOTE:

The default low flow level is 0.6 SCFH (

±

0.2). See “Adjusting the Low Flow

Setting” on page 15 to adjust this setting.

Pressure switch

The pressure switch is mounted to the opposite side of the main circuit board. The
pressure switch monitors the flow rate of the incoming gas sample.

If the flow rate falls below the preset low flow level, the pressure switch causes the fail
relay to interrupt the signal in the 4-20 mA line. This causes a downscale reading at the
monitor. The low flow level is factory-set at 0.6 SCFH (

±

0.2 SCFH).

EXHAUST fitting

The EXHAUST fitting on the right side of the housing allows the gas sample to exit the
sample draw detector. The EXHAUST fitting accepts 1/4 in. rigid tubing. See the
Installation section on page 7 to connect tubing to the EXHAUST fitting.

Detection System

The detection system consists of the combustible gas sensor, the hydrogen transmitter,
and the main circuit board.

Combustible gas sensor

The combustible gas sensor is installed in a cavity block. The cavity block is mounted to
the aluminum

subpanel near the bottom of the sample draw detector. The combustible

gas sensor includes the sensing elements, flame arrestor, connector, and sensor leads.

NOTE:

The cavity block includes a cavity for an oxygen sensor. This version of the

sample draw detector does not include the oxygen sensor.

Sensing elements

Two sensing elements are protected within the sensor assembly. Through a series of
thermal and electronic reactions, these elements produce an output that is proportional to
the detection range of the sample draw detector. The transmitter converts the output to a 4
- 20 mA signal which can be used by a recording or monitoring device.

The porous flame arrestor allows the gas sample to enter the sensor assembly and contact
the sensing element. The flame arrestor also contains sparks within the sensor.

Advertising