35-3010RKA-08 Sample-Draw Detector • 3

mounting feet to install the housing to a vertical surface. Use the two conduit hubs on the
bottom of the housing to make wiring connections.

An aluminum subpanel is mounted to the interior of the housing. The sample-draw
detector’s internal components are mounted to the subpanel.

Flow System

The sample-draw detector’s flow system consists of the INLET fitting, hydrophobic filter,
charcoal filter, pump, flowmeter, bypass valve, status lights, pressure switch, flow blocks,
and EXHAUST fitting (see Figure 1). Figure 2 illustrates how the gas sample moves
through the flow system.

Figure 2: Sample Draw Detector Flow Diagram

INLET Fitting

The INLET fitting on the bottom of the housing allows the gas sample to enter the sample-
draw detector. The INLET fitting accepts 1/4 in. rigid tubing. See “Installation” on
page 10 for instructions to connect tubing to the INLET fitting.

Hydrophobic Filter

The hydrophobic filter is to the left of the main circuit board. It is held in place by a metal
clip. It prevents water and other liquids from contaminating the flow system. Replace the
filter when it appears dirty, discolored, or clogged. If a liquid other than water is drawn
into the filter, replace the filter as soon as possible.

Charcoal

Filter

CO

Dum my

Plug

Pressure Switch

H2S

Dum my

Plug

IR CH4

Oxygen

Flow meter

Bypass

Valve

Flow Block

LEL

Dum my

Plug

Pump

Exhaust

Inlet

Hydrophobic

Filter