Overview

This manual describes the 65-2397RK CO

2

transmitter. This manual also describes how to

install, start up, configure, maintain, and calibrate the transmitter when it is used with a
gas monitoring controller. A parts list at the end of this manual lists replacement parts and
accessories for the CO

2

transmitter.

Specifications

Table 1 lists specifications for the CO

2

transmitter.

WARNING: When using the 65-2397RK, you must follow the instructions and warnings

in this manual to assure proper and safe operation of the 65-2397RK and to
minimize the risk of personal injury. Be sure to maintain and periodically
calibrate the 65-2397RK as described in this manual.

Table 1:Specifications

Description

Specification

Target Gas

Carbon Dioxide (CO

2

)

Sampling Method

Diffusion

Signal Output

4 to 20 mA

Detection Range

65-2397RK-02: 0-5,000 ppm

65-2397RK-03: 0-5% Volume

65-2397RK-05: 0-50% Volume

65-2397RK-10: 0-100% Volume

Response Time

90% in 45 seconds

Operating Temperature

-4°F to 122°F (-20°C to 50°C)

Accuracy

± 5% of reading or ± 2% of full scale (whichever is greater)