Calibration

This section describes how to calibrate the combustible gas transmitter. It includes
procedures to prepare for calibration, enter the Calibrate program, set the zero reading, set
the response reading, and return to normal operation.

NOTE:

Calibrating the transmitter may cause alarms. Be sure to put the controller into

calibration mode or disable external alarms before calibration.

Preparing for Calibration

1.

Slide the calibration cup over the bottom of the combustible gas detector, then secure
the calibration cup to the detector with the thumb screw.

2.

Use the sample tubing to connect the regulator to the calibration cup.

NOTE:

Do not screw the regulator into the zero air calibration cylinder at this time. If
you can verify a fresh air environment, you will not need to apply gas from the

zero air cylinder when setting the zero.

3.

Set a voltmeter to measure in the millivolt (mV) range.

WARNING: Do not remove the junction box cover while the circuits are energized

unless the area is determined to be non-hazardous. Keep the junction box

cover tightly closed during operaiton.

4.

Remove the junction box cover, then plug the voltmeter leads into the test points on
the amplifier.

Plug the positive lead into the test point labeled

TP+

; plug the negative lead into the

test point labeled

TP-

.

5.

Use the following formula to determine the correct test points output for the
calibrating sample.

Output (mV) = (calibrating sample/fullscale) X 400 + 100

For example, with a calibrating sample of 50% LEL and a fullscale setting of
100% LEL, the correct output is 300 mV.

300 (mV) = (50/100) X 400 +100

Setting the Zero Reading

1.

Screw the regulator into the zero air calibration cylinder.

2.

When the reading on the voltmeter stabilizes, verify a reading of 100 mV (±2 mV).
If necessary, use the zero potentiometer on the amplifier to adjust the reading to
100 mV (±2 mV).

3.

Unscrew the regulator from the zero air calibration cylinder.

Leave the sample tubing connected to the regulator and the calibration cup.

Setting the Response Reading

1.

Screw the regulator into the calibration cylinder.

2.

When the reading on the voltmeter stabilizes, verify that the reading matches the