Installation – RKI Instruments 65-2400RK-05 User Manual

Page 5

Advertising
background image

Combustible Gas Transmitter • 5

Installation

This section describes procedures to mount the combustible gas transmitter in the
monitoring environment and wire the transmitter to a controller.

Mounting the Combustible Gas Transmitter

1.

Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.

Select a site where the transmitter is not likely to be bumped or disturbed. Make
sure there is sufficient room to perform start-up, maintenance, and calibration
procedures.

Select a site where the target gas is likely to be found first. For lighter gases,
mount the detector near the ceiling; for heavier gases, mount the detector near the
floor.

Figure 2: Mounting the Combustible Gas Transmitter

If the combustible gas detector is mounted to the junction box, skip to step 5. If not,
continue with step 2.

NOTE: The LEL detector is normally provided with a Killark HKB junciton and an HFC

lid rated explosion proof for ClassI, Groups B, C, and D. This combination is
shown in Figure 2 above. Any junction box with an internal volume less than or
equal to 69 cubic inches and rated explosion proof for ClassI, Groups B, C, and D

may be used.

2.

Remove the junction box cover.

3.

Guide the four wires that extend from the top of the combustible gas detector through

3/4 Conduit Hub

3.94

2.3 max

1.1

5.46

2.75

5.2

Ø .25 Mounting Holes, 2X

6.1

7.7 max

Advertising