Combustilbe Gas Transmitter • 14

response reading (±2 mV) you determined earlier. If necessary, use the span
potentiometer on the amplifier to adjust the reading to match the correct response
reading.

3.

Unscrew the regulator from the calibration cylinder.

4.

Remove the voltmeter leads from the amplifier test points.

5.

Loosen the two screws that secure the calibration cup to the detector, then remove the
cup from the bottom of the detector.

NOTE:

For convenience, leave the components of the calibration kit connected by the
sample tubing.

6.

Secure the junction box cover to the junction box.

7.

Wait one to two minutes for the reading to decrease and stabilize.

8.

Verify that the display reading at the controller decreases and stabilizes at 0 %LEL.

9.

Store the components of the calibration kit in a safe and convenient place.

Parts List

Table 5 lists replacement parts and accessories for the combustible gas transmitter.

Table 5: Parts List

Part Number

Description

06-1248RK

Sample tubing (3/16 in. x 5/16 in.; specify length when ordering)

18-0003RK

Conduit plug (3/4 in. NPT)

18-0405RK-01

Junction box (without cover, pre-drilled for amplifier)

18-0406RK

Junction box cover (cover only)

57-1050RK

Amplifier (specify target gas when ordering)

61-0140RK-05

Combustible gas detector (specify target gas when ordering)

65-2400RK-05

Combustible gas transmitter (includes detector and amplifier;
specify target gas when ordering)

71-0052RK

Combustible Gas Transmitter Manual Insert (this document)

81-0007RK-01

Calibration cylinder (50% LEL Hexane; 34 liter)

81-0012RK-01

Calibration cylinder (50% LEL Methane; 34 liter)

81-0076RK-01

Zero air calibration cylinder (34 liter)

81-1003RK

Regulator, 0.5 liter/minute; continuous flow
(for 17 and 34 liter calibration cylinders)

81-1117RK

Calibration cup