RKI Instruments 65-2432RK User Manual

Page 17

Advertising
background image

65-2432RK CO Transmitter • 17

mV (± 2mV).

3.

Unscrew the regulator from the zero air calibration cylinder.

Leave the sample tubing connected to the regulator and the calibration cup.

Setting the Response Reading

1.

Screw the regulator into the calibration cylinder. Gas will begin to flow.

2.

Allow the gas to flow for two minutes, then verify that the reading matches the
response reading (± 2mV) you determined earlier. If necessary, use the span
potentiometer on the amplifier to adjust the reading to match the correct response
reading.

3.

Unscrew the regulator from the calibration cylinder.

Returning to Normal Operation

1.

Remove the voltmeter leads from the amplifier test points.

2.

Unscrew the calibration cup from the detector.

NOTE:

For convenience, leave the components of the calibration kit connected by the
sample tubing.

3.

Secure the junction box cover to the junction box.

4.

When the display reading falls below the alarm setpoints, return the controller to
normal operation.

5.

Verify that the controller display reading decreases and stabilizes at 0 ppm.

6.

Store the components of the calibration kit in a safe and convenient place.