65-2432RK CO Transmitter • 7

Junction Box

Use the junction box to install the CO transmitter at a mounting site that is remote from
the controller. The junction box also protects the amplifier and wiring connections made
to the amplifier. Use the two 3/4 in. conduit hubs to mount the detector to the junction
box (bottom hub) and connect wiring from the amplifier to the controller (top hub).

NOTE:

The CO detector and amplifier are factory-mounted to the junction box.

Use the junction box’s two mounting holes to mount the CO transmitter to a vertical
surface at the monitoring site. Use the cover on the front of the junction box to access the
interior of the junction box.

Installation

This section describes procedures to mount the CO transmitter in the monitoring
environment and wire the transmitter to a controller.

Mounting the CO Transmitter

1.

Select a mounting site that is representative of the monitoring environment.
Consider the following when you select the mounting site.

Select a site where the transmitter is not likely to be bumped or disturbed. Make
sure there is sufficient room to perform start-up, maintenance, and calibration
procedures.

Select a site where the target gas is likely to be found first.

NOTE:

If your application does not require a specific mounting site, mount the

transmitter at approximately breathing level.

Figure 2: Mounting the CO Transmitter

3/4 Conduit Hub

3.94

1.1

6.1

2.75

5.2

5.46

Ø .25 Mouting Holes (2X)

2.85 max

8.3 max