RKI Instruments 65-2640RK-04 User Manual

Page 19

Advertising
background image

65-2640RK-04 M2A Transmitter Operator’s Manual

14

NOTE:

If the M2A is being wired to a PLC or DCS device, see “Appendix B: PLC and
DCS Device Wiring” on page 49, then continue with step 8.

Use the following recommendations to determine how to wire the M2A:

If Modbus connections will not be used and only the PWR/SIG connections will
be used, use a two or three conductor shielded cable or two or three wires in
conduit for connections to the power/signal terminal strip depending on whether
or not the signal (S) terminal is used. The S terminal has a 4 - 20 mA output, but if
you do not need to monitor this signal and do not connect to the S terminal to
access this signal, the M2A will still function completely.

If the PWR/SIG connections and one or more relays are used, route the
connections to the M2A in conduit. Use shielded cable in the conduit for the
PWR/SIG connections and unshielded cable or individual wires for the relay
connections. Make sure any wire or cable used for relay wiring is appropriately
rated for the power that it will carry.

CAUTION:

If shielded cable is used for the PWR/SIG connections, leave the cable shield’s drain
wire insulated and disconnected at the M2A junction box. You will connect the
opposite end of the cable’s drain wire at the controller or device.

If the M2A will be wired into a Modbus network, see “Chapter 8: RS-485 Modbus
Output” on page 37.

Table 3: Wire Size for PWR/SIG Connections

Max Distance to Controller

w/18 Gauge Wire

Max Distance to Controller

w/16 Gauge Wire

Max Distance to Controller

w/14 Gauge Wire

2,500 ft.

5,000 ft.

8,000 ft.

Advertising