Supported modbus functions – RKI Instruments 65-2640RK-04 User Manual

Page 47

Advertising
background image

65-2640RK-04 M2A Transmitter Operator’s Manual

42

Supported Modbus Functions

The M2A supports Function Code 03: Read Holding Registers and Function Code 16:
Write Registers.

Function Code 03: Read Holding Registers

There are a total of 40 registers available to be read via this Function Code.

Registers 1 - 2

The format (bit & field assignments) for registers 1 - 2 is shown below in Table 10 -
Table 11.

Table 10: Register 1, Numerical Reading with Sign & Decimal Point Bit & Field Assignments

Bit(s)

Value & Field

[15]

Sign of Reading
0 = Positive
1 = Negative

[14:13]

Format of Reading
0 = XXX (no decimal point)
1 = XX.X
2 = X.XX
3 = .XXX

[12:0]

Numerical value of display reading (8000 max)

Table 11: Register 2, Operating State, Alarms & Relays Bit & Field Assignments

Bit(s)

Value

[15:12]

Operating State
0 = Undefined
1 = Initialization
2 = Normal
3 = Warm-up
4 = Fail
5 = Calibration
6 = Post-Calibration
7 = Low Power
8 = Setup

[11]

Gas Type Change
0=Not Changed
1=Changed

[10]

Configuration Change
0=Not Changed
1=Changed

[9]

Calibration Activity Flag
0=No Calibration Activity
1=Calibration Activity Has Occurred

Advertising