Model GD-70D4H-XX Sample Draw Transmitter • 6

the opposite end of the tubing to an open area where the sample can safely disperse or
to an exhaust duct.

Wiring the GD-70D to a Controller and AC Power

WARNING: Always verify that power to the GD-70D4H-XX and to the controller are

off and that the controller’s and GD-70D’s power switches are in the off
position before making wiring connections or adjustments.

1.

Turn off power to the controller and the GD-70D4H-XX.

2.

Place the controller’s and GD-70D’s power switches in the OFF position.

3.

Use the conduit hubs at the bottom of the GD-70D4H-XX for routing power and
signal cables into the enclosure. Route a 3-wire power cable (18 AWG) and any relay
wiring through one conduit hub, and 2-conductor shielded cable, or two wires in
conduit through the other conduit hub to minimize crosstalk.

Figure 4: External Wiring

4.

If shielded cable is used for controller wiring, connect the signal cable shield’s drain
wire to a chassis ground at the controller, but do not connect it at the GD-70D4H-XX.

CAUTION:

Leave the cable shield’s drain wire insulated and disconnected at the
GD-70D4H-XX. You will connect the opposite end of the cable shield’s drain wire at
the controller.

1

2

3

4

5

6

7

+

+

-

-

ALM1

DC24V 4-20mA

ALM2

FAULT

+

-

-

+

GD-70D Terminal Strip

8

9

10

From

Power
Supply

Alarm
Device

Alarm
Device

(+) H

AC Terminal Strip

Strobe

Light

100-240 VAC

H

N

G

4 - 20 mA In (FB)

- (DC Ground)

Controller

(-) N

External Power

Source

+ (No Connection)

(+) H

(-) N

External Power

Source