18. TROUBLESHOOTING GUIDE

SET THERMOSTAT TO CALL FOR HEAT

IS THE HEATER BURNING?

THE SYSTEM IS WORKING PROPERLY.
STOP.

YES

NO

IS THERE LINE VOLTAGE TO
THE THERMOSTAT CONTROL?

→CHECK CIRCUIT BREAKERS OR FUSE
→CHECK ON/OFF SWITCH
→CHECK NIGHT TIME SET BACK CONTROL

NO

IS THERE VOLTAGE TO THE
FAN SYSTEM?

YES

YES

→CHECK ELECTRICAL CONNECTION
FROM THERMOSTAT TO FAN MOTOR
→CHECK THERMOSTAT, REPLACE IF
NECESSARY

NO

IS FAN MOTOR OPERATING?

→CHECK EXHAUST FAN MOTOR, REPLACE
IF

NECESSARY

NO

IS THERE VOLTAGE TO THE
TRANSFORMER?

YES

→CHECK ELECTRICALCONNECTION
TO

TRANSFORMER

→CHECK LINE VOLTAGE TO PRIMARY
SIDE OF TRANSFORMER

YES

NO

IS THERE VOLTAGE FROM TRANS-
FORMER TO AIR-PROVING SWITCH?

→CHECK ELECTRICAL CONNECTION FROM
TRANSFORMER TO AIR SWITCH
→CHECK TRANSFORMER, REPLACE IF
NECESSARY

NO

YES

CONT’D

→CHECK FOR DARK SPOTS OR LINES ON
THE TILE SURFACE
→’DARK’ AREAS REPRESENT CRACKS OR
BLOCKAGE OF THE TILE
→SEE ’SERVICE’ SECTION 15