Schwank supraSchwank User Manual

Page 24

Advertising
background image

supra/primo Manual

IM091112

RD: APR 2013

RL: 13B

24

IS THERE VOLTAGE FROM AIR-
PROVING SWITCH TO IGNITION
CONTROL MODULE?

→CHECK ELECTRICAL CONNECTION FROM AIR
SWITCH TO IGNITION CONTROL MODULE.
→ENSURE LOW VOLTAGE WIRES ARE
PROPERLY INSTALLED, WIRING POLARITY
IS CRITICAL
→CHECK VA RATING ON THE TRANSFORMER.
→ENSURE AIR HOSE IS CONNECTED

PROPERLY FROM A I R

S W I T C H

T O

EXHAUST

FAN

→CHECK AIR SWITCH, REPLACE IF
NECESSARY

YES

NO

IS THERE A SPARK AT IGNITION
SPARK IGNITER?

→ENSURE THE IGNITER GAP IS 1/4" WIDE
(6MM)
→ENSURE THE FLAME SENSOR IS WITHIN
1/4” TO 1/8" ABOVE CERAMIC TILE
→CHECK SPARK IGNITER CE RAMIC FOR
CRACK, REPLACE SPARK IGNITER IF NECES
SARY
→CHECK HI-VOLTAGE WIRE C O N N E C T I O N
FROM SPARK IGNITER TO IGNITION MODULE
→ENSURE HIGH VOLTAGE S P A R K S

A R E

GENERATED ON THE IGNITION CONTROL
TERMINAL BY FOLLOWING THE STEPS AS
SHOWN

BELOW:

-SHUT OFF ELECTRICAL POWER
-REMOVE THE HI-VOLTAGE WIRE ON THE
IGNITION CONTROL TERMINAL

WARNING: BEFORE REMOVING HI-VOLTAGE
WIRE, ELECTRICAL POWER TO THE SYSTEM
MUST BE SHUT OFF. THIS TERMINAL CARRIES
15,000 AC VOLTS.

 TURN ON ELECTRICAL POWER

 PLACE A METAL CONDUCTOR 1/8" AWAY
FROM THE HI-VOLTAGE TERMINALS

WARNING: THE HANDLE ON THE METAL
CONDUCTOR MUST BE HEAVILY INSULATED.
A LONG SCREW DRIVER WITH THICK PLASTIC
INSULATION HANDLE IS IDEAL FOR THIS

APPLICATION.

 IF NO SPARKING OCCURS ACROSS THE

GAP TO THE METAL CONDUCTOR

,

THEN

THE IGNITION CONTROL IS DEFECTIVE.

REPLACE WITH NEW IGNITION CONTROL. -

SHUT OFF ELECTRICAL POWER AND RE-

CONNECT THE HI-VOLTAGE WIRE

.

YES

NO

CONT’D