IS THERE VOLTAGE FROM IGNITION
CONTROL TO COMBINATION GAS
VALVE?

→

CHECK ELECTRICAL WIRES FROM IGNITION

CONTROL TO COMBINATION GAS VALVE

→

CHECK IGNITION CONTROL, REPLACE IF

NECESSARY

NO

IS GAS COMING THROUGH
ORIFICE ON THE HEATER?

YES

→

ENSURE ALL GAS VALVES ARE OPEN

NO

YES

DOES THE IGNITION CONTROL
TERMINATE THE SPARKING
PROCESS AFTER THE HEATER IS
OPERATING?

→

CHECK SPARK IGNITER FOR CRACKS,

REPLACE SPARK IGNITER IF NECESSARY
→ENSURE THE SENSING WIRE IS SECURELY
CONNECTED TO THE SENSING PROBE
→CLEAN THE SENSING PROBE ON THE SPARK
IGNITER
→ENSURE THE FLAME SENSOR IS WITHIN 1/4"

ABOVE THE CERAMIC TILE

→CHECK FLAME SIGNAL WITH METER, IF LOW
CHANGE

SENSOR

→REPLACE WITH NEW IGNITION CONTROL
UNIT IF OTHER CHECKS ARE OK

DOES HEATER SHUT DOWN

AFTER IGNITION CEASES?

→CHECK FLAME SIGNAL USING A METER
INSTALLED IN SERIES WITH SENSOR CABLE,
CHECK (MICROAMPS) STRENGTH OF SIGNAL
FOR 1.5uA MINIMUM

YES

YES

NO

NO

STILL HAVING TROUBLE

OPERATING THE HEATER?

→REPEAT THE ABOVE TROUBLE SHOOTING
PROCEDURES
→IF THE PROBLEM PERSISTS, CONTACT YOUR
SCHWANK DISTRIBUTOR.

YES

NO

TROUBLESHOOTING
COMPLETE

→IF SIGNAL IS LOW REPLACE SENSOR AND
WIRE