Tube heater length + combustion air duct + vent – Schwank premierSchwank IQ User Manual

Page 33

Advertising
background image

33

STS-JZ-F / IQ-F I&O Manual

IM101220

RD: AUGUST 2014

RL: 18A

V

ERTICAL

VENT

THROUGH

THE

ROOF

:

It is the sole responsibility of the installer to ad-
here to all current local codes and/or ANSI
Z223.1 / CSA.B149.1 latest editions for all vent-
ing requirements, and practices.



Use an approved ‘B-vent’ termination cap as
supplied by the manufacturer of the approved
‘B-vent’.



When vent and combustion air are taken
through the roof, the exhaust vent should al-
ways terminate higher than the combustion
air intake, to prevent recycling the products of
combustion back into the heater



At most a quantity of three 90° elbows can be
installed in a vertical vent

Approved
Cap

Approved
‘B’ Vent

24” Min

60 cm

12

9

If roof slope exceeds 9:12
consult NFPA-54 ANSI
Z223.1 or CSA-B149.1

FIGURE 22

Up

to

12A. Combined System Length: Tube Heater + Vent + Combustion Air Duct

:

MINIMUM VENT LENGTH: (Vented or Unvented [indirect mechanical ventilation])



Minimum vent length of 3 ft (91 cm) is required (

NOTE: 200,000 LP: Minimum 8 ft (244 cm)

MAXIMUM SYSTEM LENGTH (includes:

Tube Heater length + combustion air duct + vent

):



Each 90° elbow in the system has an equivalent length of 5 ft.



A maximum of 2 elbows are allowed in any portion (duct, tube heater, vent) with the ex-
ception of up to three 90° elbows in a vertical vent run through the roof



Combustion air duct may be 4” or 5” diameter and is not to exceed lengths in table below

 Exceeding the allowable lengths in the table below can create combustion and/or conden-

sation problems and will void CSA Certification and the heater warranty.

 Do not exceed the Maximum Combined System Length regardless of the allowed maxi-

mum length of individual vent or combustion air duct

Input

(Btuh)

Do Not Exceed

Maximum Combined

System Length

Max. Vent

Length

Individual: 4ӯ

OR

Combined: 6ӯ

4”

Air Duct 5” Air Duct

4”

Ш

5”

Ш

45,000

& 60,000

60 ft

80 ft

20 ft

40 ft

20 ft

80,000

70 ft

90 ft

20 ft

40 ft

20 ft

100,000

60 ft

80 ft

30 ft

50 ft

30 ft

110,000

to 150,000

100 ft

120 ft

30 ft

50 ft

30 ft

175,000

& 200,000

120 ft

140 ft

30 ft

50 ft

40 ft

Max. Air Duct

Length

(by Duct Diameter)

Example

150,000 Btuh Heater:

Tube Heater Length 50 ft

1 x 90° elbow (vent)

5 ft

Straight vent

20 ft

1 x 90° elbow (duct)

5 ft

Air Duct: 4” Ø

17 ft

Combined Length

97 ft

Max. Allowed

100 ft

Additional 20’ for 5” Ø Air Duct

INSTALLATIONS UP TO 4500 FEET (Higher altitudes refer to Section 27)