Schwank premierSchwank IQ User Manual

Page 7

Advertising
background image

7

STS-JZ-F / IQ-F I&O Manual

IM101220

RD: AUGUST 2014

RL: 18A

TABLE 1 MINIMUM CLEARANCES TO COMBUSTIBLES*

FIGURE 1 MINIMUM CLEARANCES TO COMBUSTIBLES* - refer to Table 1 for values

*The clearance to combustible materials represents the minimum distance that must be main-

tained between the heater and a nearby surface. The stated clearance to combustibles
represents a surface temperature of 90F° (50C°) above room temperature.
.

NOTE: A ‘PEEL & STICK’ SIGN IS SUPPLIED: USE AN INDELIBLE MARKER TO

ENTER VALUES ‘H’, ‘S’, ‘F’, & ‘B’ ON .

POST THE SIGN ADJACENT TO THE HEATER THERMOSTAT OR IN A
PROMINENT LOCATION.

See next page for details.

F

D

B

A

S

S

C

Suspended at an
angle up to 45°

Suspended
horizontally

C

FLOOR

H

T

H

M a x i m u m
Stack Height
H = T- C

‘T’ is meas-
ured on site,

FLOOR

T

M a x i m u m
Stack Height
H = T- C

‘T’ is meas-
ured on site,

MODEL

SUSPENDED AT AN ANGLE

UP TO 45 DEGREES

SUSPENDED

HORIZONTALLY

D

inches (cm)

B

inches (cm)

F

inches (cm)

C

inches (cm)

A

inches (cm)

S

inches (cm)

C

inches (cm)

STS-JZ / IQ 200 13

(33)

6 (15.2)

74

(188)

70

(178)

14 (36)

44 (112)

76

(193)

STS-JZ / IQ 175 12

(31)

6 (15.2)

72

(183)

68

(172)

13 (33)

42 (107)

74

(188)

STS-JZ / IQ 155 5.5

(14)

1 (2.5)

64

(163)

64

(163)

3.5 (9)

22 (48)

70

(178)

STS-JZ / IQ 130 4.5

(11)

1 (2.5)

60

(152)

60

(152)

3.3 (9)

21 (28)

65

(165)

STS-JZ / IQ 110 3.5 (9)

1 (2.5)

54

(137)

54

(137)

2 (5)

19 (25)

60

(137)

STS-JZ / IQ 100 6.5

(16.5)

1 (2.5)

57

(145)

68

(172)

6 (15)

22 (56)

68

(172)

STS-JZ / IQ 80 3 (8)

1 (2.5)

23 (59)

38 (97)

1.75 (5)

6 (15)

38 (97)

STS-JZ / IQ 60 2.5 (6)

1 (2.5)

17 (43)

34 (86)

1.5 (4)

5.5 (14)

34 (86)

STS-JZ / IQ 45 2.75 (7)

1 (2.5)

24 (61)

32 (81)

2.25 (6)

7 (18)

32 (81)

Advertising