7. GAS SUPPLY PIPING



All piping must be installed according to applicable local and national codes



A listed flexible connector (field supplied) must be installed between the heater and gas
supply piping. For outdoor installation the connector must be in compliance with
ANSI Z21.75 / CSA 6.27. A 1/2” x 24” stainless steel flexible gas connector (JL-0771-XX
- approved Indoor/Outdoor) is available as an option from Schwank / InfraSave.



A drip-pocket must be provided at the inlet connection



Provide a 1/8” NPT plugged tapping, accessible for test gage connection, immediately
upstream of the gas supply connection to the heater.



On propane-fired units, a main line filter is recommended (field supplied)



Piping joint compounds must be resistant to the action of liquefied petroleum gases



All piping joints must be tested for leaks with a soap and water solution.

CAUTION: DO NOT INSTALL ANY GAS PIPING IN HEAT ZONES

The maximum supply pressure must be limited to 14”w.c. (0.5 psi). If the line pressure is
above 14”w.c., then a separate pressure reducing regulator must be installed. The minimum
pressure at the inlet to the heater regulator must be equal to or greater than 6.0”w.c. for natu-
ral gas and 11.0”w.c. for propane gas.
Proper manifold pressure must be established during commissioning, and will be maintained
when the main burner is operating under the following supply pressure:

7.1 GAS PRESSURE

Table 5

LINE PRESSURE “w.c. MANIFOLD PRESSURE “w.c.

MINIMUM MAXIMUM AT GAS VALVE TEST POINT

NATURAL GAS

6.0

14.0

5.0

PROPANE GAS

11.0

14.0

10.0

Natural Gas: Orifice sized for 1000 BTU/CU.FT.
Propane Gas: Orifice sized for 2500 BTU/CU.FT.

8. BASIC ELECTRICAL REQUIREMENTS - see also Section 16 page 25

All electrical installations must meet local codes and the latest edition ANSI/NFPA N0 70 in the
U.S.A. and Electrical Code PART 1 CSA C22.1 in Canada .

TRANSFORMER SPECIFICATIONS (field supplied)

Single heater requires 24 Volt, 60 Hz electrical transformer sized at 40 VA.

Multiple heaters in a zone are powered by a single transformer (field supplied). The proper
transformer is 24 Volt AC, 60 Hz, sized at 40VA for the first heater plus 20VA for each addi-
tional heater in the zone - round up the calculated value to the next higher available sized
transformer. For example, four heaters in a zone require a transformer of : 1 x 40VA + 3 x 20
VA = 100 VA . It is not recommended to install more than 12 heaters per zone.