Schwank supremeSchwank IO-210 User Manual

Page 20

Advertising
background image

2300 / IO 210 Manual

IM110107

RD: MAY 2014

R.L. 15A

20

MODEL

Voltage

VAC

Current

amps

Btu/hr input

Total

Weight (lbs).

Length

< A >

2312 / IO 212 -NG
2312 / IO 212 -LP

2313 / IO 213 -NG
2313 / IO 213 -LP

24

40 VA*

23,000
23,000

35,000
35,000

32
32

44
44

30 1/2”
30 1/2”

43 1/2”
43 1/2”

14. HEATER DIMENSIONS & CONFIGURATIONS

Figure 5: DIMENSIONS

Front View

End View

Table 5: CAPACITIES & CONFIGURATIONS

* For a multiple heater installation, the first heater is sized at 40VA and each consecutive
heater is sized at 20VA. The sum total will be the required Transformer size. If total VA
exceeds one transformer size select the next higher VA rated transformer.

15. MOUNTING KIT OPTIONS (NOTE: For unusual mounting application contact

manufacturer.)

ITEM NO

PART NUMBER

DESCRIPTION

1

JP-2300-MB

WALL MOUNTING BRACKET

2

JP-2300-MK

ARM MOUNTING BRACKET

3

JP-2300-PK

POST BRACKET

The heater is supplied with chain mounting bracket JP-2300-HS
Other optional mounting kits are available:

WARNING: Wall Mounting Bracket JP-2300-MB, or Arm Mounting Bracket JP-2300-MK:

Ensure that anchoring to the structure is of sufficient strength, integrity and
workmanship, to adequately support the weight of the heater and any other
potential loads such as snow build up.

A

10”

13”

Advertising
This manual is related to the following products: