Schwank SEB(U) User Manual

Page 13

Advertising
background image

SP-MSEB-BX-10A

SEB Manual

RD: JUNE 2004

RL: 10

KH

1. Reflectors
2. 90

0

Elbow

3. End of Swaged Tube (fully inserted)
4. Couplers

9. REFLECTOR INSTALLATION

After burner and tubes have been installed,
slide the focus shield reflectors one at a time
into the wire hangers. As each successive
focus shield reflector is installed on an in-line
installation, the ends of the focus shield
reflectors will overlap to provide continuous
coverage over the entire tube system. The
overlapping joints MUST BE FASTENED
together.
Note that for both horizontal and angle
mounting, the tube must be level. Improper

mounting can result in overheating of
controls and combustible materials. Use only
non-combustible mounting hardware. Side
reflectors can be added to the heaters as an
option. They should be secured directly to
the focus shield reflector using "S" hooks or
chain. Drill three holes into the focus shield
reflector flange along side, matching up with
three holes already in side reflector. Mount
side reflector as close as possible to the focus
shield reflector.

FIGURE 9 90 DEGREE ELBOW INSTALLATION

Page 9

(1)

(2)

(3)

(4)

Advertising