Page 2 – Schwank SEB(U) User Manual

Page 6

Advertising
background image

SP-MSEB-BX-10A

SEB Manual

RD: JUNE 2004

RL: 10

KH

*Manufactured and shipped in 10’ lengths. Due to the swaged overlap total lengths are slightly shorter
than multiples of 10’. Overall length includes the Burner (and Turn Box for U models). Where required,
the series SEB/U heaters will be supplied with the turbulators, snugly installed into the end tube(s).

Page 2

TABLE 1: MODEL

CONFIGURATIONS

OVERALL

HEATER

LENGTH *

BTU/HOUR INPUT

0 TO 4500 FT ABOVE **

SEA LEVEL

TURBULATOR

REQUIRED

LENGTH

GAS

PRESSURE &

ELECTRICAL

SHIPPING

WEIGHT

(LBS.)

SEB 200-70

69 4”



200,000



10’

LINE

MINIMUM

5" W.C. N.G.

11" W.C. L.P.








LINE

MAXIMUM

14" W.C. N.G.

14" W.C. L.P.







MANIFOLD

3½" W.C. N.G.

10" W.C. L.P.

½" INLET






ELECTRICAL

120V, 60 HZ

328

SEB 200-60

59’ 8”

10’

283

SEB 200-50

50’ 0”

10’

239

SEBU 200-30

31’ 11”

10’

287

SEB 175-70

69’ 4”



175,000



10’

240

SEB 175-60

59’ 8”

10’

283

SEB 175-50

50' 0”

10’

239

SEBU 175-30

31’ 11”

10’

287

SEB 155-60

59’ 8”




155,000




Not Required

283

SEB 155-50

50’ 0”'

Not Required

239

SEB 155-40

40' 4”

10'

199

SEBU 155-30

31’11”

Not Required

287

SEBU 155-20

22' 3”

10'

199

SEB 130-50

50' 0”



130,000



Not Required

239

SEB 130-40

40’ 4”

10'

195

SEB 130-30

30’ 8”

14'

150

SEBU 130-20

22’ 3”

10'

199

SEB 110-50

50’ 0”



110,000



Not Required

239

SEB 110-40

40’ 4”

10'

195

SEB 110-30

30’ 8”

14'

150

SEBU 110-20

22’ 3”

10'

199

SEB 80-40

40’ 4”



80,000



10’

195

SEB 80-30

30’ 8”

14'

150

SEB 80-20

21’ 0”

14'

106

SEBU 80-10

12’ 7”

14'

110

SEB 60-30

30’ 8”


60,000


14’

150

SEB 60-20

21’ 0”

14'

106

SEBU 60-10

12’ 7”

14’

106

SEBU 130-15

17’ 3”

14’

150

SEBU 110-15

17’ 3”

14’

154

** 2000 feet above sea level for the USA – see Orifice Altitude Conversion Chart on page 29