Troubleshooting guide for ser / ir-60 – Schwank SER(IR) User Manual

Page 24

Advertising
background image

GP-MSER-BX-11A

SER / IR Manual

RD: March 2006

RL: 11A

KH

Legend:

MCU = Main Control unit
PSW = Air Pressure Switch
HV = High Voltage

YES

YES

YES

Page 20

20. TROUBLESHOOTING GUIDE FOR SER / IR-60

SET THERMOSTAT TO CALL FOR HEAT

COMBUSTION AIR BLOWER STARTS

NO

YES

NO

CHECK WIRING CONNECTION AND
REPLACE BLOWER MOTOR IF DEFECTIVE

AIR PROVING SWITCH CLOSED
110 VOLTS AT INGITION CONTROL

NO

Æ ENSURE THAT THE AIR INTAKE AND FLUE
ARE NOT BLOCKED
Æ ENSURE PRESSURE TUBE IS CONNECTED AND
NOT BLOCKED
Æ CHECK AIR PRESSURE WITH MANOMETER
Æ CHECK AIR PROVING SWITCH IS CLOSING
WHEN BLOWER IS RUNNING
Æ REPLACE DEFECTIVE SWITCHES

SPARK ACROSS IGNITER OR
IGNITER/SENSOR GAP

NO

ÆPLEASE SEE APPENDIX 1 SPARK IGNITION
CIRCUIT
Æ PULL IGNITION LEAD AND CHECK SPARK
Æ CHECK SPARK GAP, ADJUST TO 3/16” IF
NEEDED USING THE GROUND PRONG ONLY
Æ SPARK OK?

REPLACE IGNITION CONTROL

Æ CHECK IGNITION CABLE, GROUND WIRING
CERAMIC INSULATOR AND CAP, AND CORRECT
Æ CHECK BOOT OF THE IGNITION CABLE FOR
SIGNS OF MELTING OR BUCKLING
Æ TAKE PROTECTIVE ACTION TO SHIELD CABLE
AND BOOT FROM EXCESSIVE TEMPERATURES

CHECK THERMOSTAT

CONTINUES ON NEXT PAGE

CHECK FOR LINE VOLTAGE POWER SUPPLY