SP-MSTP-AC-15A

STS-p Manual

RD: DEC, 2003

RL:15

KH

CA SERIES: TROUBLESHOOTING GUIDE HONEYWELL S87J1034 120V THERMOSTAT

APPLY 115 VOLTS

COMBUSTION AIR BLOWER STARTS

ON 24V OPTION ONLY:
CHECK FOR II5V FROM SWITCHING RELAY.
CHECK 24V SIDE OF RELAY VOLTAGE.
CHECK 115V LINE SIDE OF RELAY VOLTAGE.
CHECK OPERATION OF BOTH CIRCUITS.

IF NO SWITCHING IS TAKING PLACE.........
......REPLACE THE SWITCHING RELAY

YES

NO

CHECK IF 115 VOLTS PRESENT AT BLOWER
IF SO............REPLACE DEFECTIVE BLOWER

A.P.S. HAS CLOSED (B.F.S. IS CLOSED)
24 VOLTS PRESENT AT DSI CONTROL

NO

CHECK AIR INTAKE AND FLUE ARE NOT OB-
STRUCTED.
CHECK PRESSURE TUBE IS CONNECTED AND
NOT BLOCKED OR KINKED.
CHECK IF AIR PROVING SWITCH IS CLOSING
WHEN BLOWER IS RUNNING.
CHECK AIR PRESSURE WITH MANOMETER.
REPLACE ANY DEFECTIVE SWITCHES.

SPARK AT IGNITER / SENSOR.

VISIBLY CHECK IF IGNITER IS SHORTING OUT.
CHECK GROUND WIRING.
REMOVE AND INSPECT IGNITER AND LEAD.
CHECK BOOT OF THE IGNITION CABLE FOR
SIGNS OF MELTING OR OVERHEATING, IF SO
TAKE PROTECTIVE ACTION TO SHIELD CABLE
AND BOOT FROM EXCESSIVE TEMPERATURES.
CHECK CERAMIC INSULATOR AND CAP.
SPARK GAP SETTING IS 3/16”. (ADJUST BY
MOVING THE GROUND PRONG ONLY.)


PERFORM IGNITION LEAD TEST (SEE SPARK
IGNITION CIRCUIT INSTRUCTIONS ON PAGE 28)
GOOD SPARK .....................REPLACE IGNITER
NO SPARK /OR WEAK .......REPLACE CONTROL

cont’d

Page 25

SET THERMOSTAT TO CALL FOR HEAT

ON 24V OPTION ONLY:
THE SWITCHING RELAY ENERGIZES,
SENDING 115 VOLTS TO THE BLOWER

YES

NO

24V TO GAS VALVE

YES