Sensaphone, Press what is, Press temp limits – Sensaphone 800 User Manual

Page 78

Advertising
background image

Sensaphone

®

Model 800 User’s Manual

76

7. Press ENTER. The Model 800 responds: “Enter.”

ENTER

PM

NOTE

Do not set temperature limits too close to normal
room temperature. Minor temperature fluctuations
could result in frequent and unnecessary alarm
dialouts.

5 .4 .2 Disabling Alarm Response to High or Low

Temperature

To disable alarm response to either high or low temperature
settings exclusively, enter the following temperature limit when
programming the selected zone. (The Model 800 will not respond
to temperatures encountered at maximum settings or beyond.)
Begin by following the key sequence shown in Section 5.4.1, and
when prompted to enter the high or low temperature value:

• Set high temperature to either +150º F or +65º C (high

temperature limit) to prevent the Model 800 from
responding to a high temperature alarm.

• Set low temperature to either -20° F or -30° C to prevent the

Model 800 from responding to a low temperature alarm.

5 .4 .3 Interrogating High and Low Temperature Limits

1. Press WHAT IS.

WHAT

IS

2. Press TEMP LIMITS.

5

TEMP LIMITS

3. Press the number key corresponding to the selected
temperature zone.

4

MAX CALLS

5

TEMP LIMITS

6

CALIBRATE

8

CLOCK

3

INTERCALL

TIME

7

RECOGNITION

TIME

9

LISTEN TIME

SOUND

0

ID NUMBER

POWER

1

CALL

DELAY

2

VOICE

REPS

Advertising