Weidmuller G108 Ultra SlimPak User Manual

Page 2

Advertising
background image

Description

Diagnostic LEDs

Output

Operation

Dynamic Deadband

The Ultra SlimPak G108 is a DIN rail mount, DC voltage or current input, limit alarm with dual

setpoints and two contact closure outputs. The field configurable input and alarm functions offer

flexible setpoint capability. Input voltage spans from 10mV to 200V and input current spans from 1mA

to 100mA can be field configured. Bipolar inputs are also accepted.

The G108 is configurable as a single or dual setpoint alarm, HI or LO trips and failsafe or non-failsafe

operation. Also included are adjustable deadbands (0.25 to 5% of full scale input) for each setpoint, a

24Vdc voltage source (isolated from line power) for transducer excitation, and a flexible DC power supply

which accepts any voltage between 9 and 30Vdc.

The G108 is equipped with three front panel LEDs. The green LED is a dual function LED labelled INPUT.

This LED indicates line power and input signal status. Active DC power is indicated by an

illuminated LED. If this LED is off, check DC power and wiring connection. If the input signal is

above 110% full scale, the LED will flash at approximately 8Hz. Below 0%, the flash rate is 4Hz.

Two red LEDs indicate the relay state for each setpoint. An illuminated red LED indicates the tripped

condition.

The G108 is equipped with two SPDT (form C) relays, rated at 120Vac or 28Vdc at 5 amperes.

Each of these relays is independently controlled by the field configurable setpoint and deadband.

The field configurable G108 limit alarm setpoints can be configured for HI or LO, failsafe or non-failsafe

operation. Each of the setpoints has respective HI or LO deadband. In a tripped condition, the

setpoint is exceeded and the appropriate red LED will illuminate. The trip will reset only when the

process falls below the HI deadband or rises above the low deadband (see Figure 1). For proper

deadband operation, the HI setpoint must always be set above the LO setpoint. In failsafe operation,

the relay is energized when the process is below the HI setpoint or above the LO setpoint (opposite

for non-failsafe). In the failsafe mode, a power failure results in an alarm state output.

LSI circuitry in the G108 prevents false trips by repeatedly sampling the input. The input must

remain beyond the setpoint for 100 milliseconds, uninterrupted, to qualify as a valid trip condition.

Likewise, the input must fall outside the deadband and remain there for 100 milliseconds to return the

alarm to an untripped condition. This effectively results in a “dynamic deadband” based on time in

addition to the normal deadband.

Load

Load

Diode

(optional)

Power

Power

MOV

0.1uF

Film

0.1uF

Film

Figure 3: AC Inductive Loads

Figure 2: DC Inductive Loads

47 ohm

1/2W

47 ohm

1/2W

Relay

Contacts

Relay

Contacts

+

-

Figure 1

Table 1: G108 Input range switch settings (SW1, 1 through 4) KEY

z = ON

Advertising