Rated data

Input

Range

Impedance

Maximum ratings/type of protection

Field device excitation

Other input specification

Other input specification

Output

Range

Load

Burnout level

Zero / Span adjustment

Protection

Other output specification

Other output specification

Supply

Range

Consumption

Other supply specification

General

Accuracy

Linearity

Temperature coefficient (drift)

Transmission frequency

Response time. 90% span

Other general specification

Status LED

Isolation (# of ports)

Operating / Storage temperature

Housing (mounting)

Dimensions

(Length x Width x Height)

Wire range (conductor size)

Insulation stripping length

Tightening torque

Approvals

Ordering data

Ultra SlimPak

Heat sink (width)

Shunt resistor

DC current or voltage

±1mA to ±100mA or ±10mVdc to ±200Vdc, DIP switch selectable

20

M for current, >100kM for voltage

170mA, 60Vdc for current, 200Vrms for voltage / self resetting fuse

24Vdc @ 20mA typical

2 form C relays (2 SPDT), one set point per relay, gold flash / silver alloy contacts

2 set points independently adjustable over 100% of the selected input span, HI or LO, failsafe or non-failsafe

maximum 5A at 120Vac, 2A at 240Vac, 5A at 24Vdc (resistive load), minimum 10

HA at 10mV

deadband adjustable from 0.25% to 5% of span (span >50mV or >5mA) and from 1% to 5% of span

(span <50mV or <5mA)

external relay contact protection required for inductive load switching

Electrical life: 10

5

operations at rated load

Mechanical life: 10

7

operations no load

DC voltage

9 to 30Vdc, inverter isolated

1.5W typ., 2.5W max. (300mA inrush at 9Vdc)

0.1% of full scale (span >50mV or >5mA), 0.2% of full scale (span <50mV or <5mA)

±0.05% of full scale/°C, max.

<250mS in normal mode, dynamic deadband: relay status will change when proper setpoint/process

condition exists for 100mS

input green (>110% of input: 8Hz, <0% of input: 4Hz), 2 setpoint red (ON: tripped, OFF: safe)

1800V (3 port) between contacts, input and power

0°C to 55°C / -25°C to 70°C

EG12 (TS32 and TS35)

90mm x 17.7mm x 112.7mm max.

22-12AWG (0.5-4.0mm

2

)

7mm

0.4-0.8Nm

CSA (file LR-42272), UL (file E99775), CE marked

(EMC dir. 89/336/EEC, LV dir. 73/23/EEC: input <75Vdc only)

Cat.No.

G108 (factory calibration: 0...20mA, A-HI/B-LO, non-failsafe)

HS01-A (1.6mm) (conditionally required depending on installation, see heat sink data)

C006 (0.1

M, 1%, 5W for use with external DC current source)

Note: G108-000X where X is the revision level

Specifications subject to change without notice. 99990010 - 8/98 Printed in Canada

TS32 RAIL

TS35 RAIL