Unless otherwise specified the factory presets the G108 as follows:

Input: Current

Range: 0-20mA

Output: Dual, SPDT

Trip: A:HI, B:LO

Failsafe: No

Deadband: A, B: 0.25%

The DC power input accepts any DC source between 9 and 30V, typically a 12V or 24Vdc source is used.

For other I/O ranges, refer to table 1 and Figure 4. Reconfigure switches SW1 for the desired input

type, range and function.

Do not attempt to change any settings with power applied. Severe damage will result!

1. With DC power off, position 9 and 10 of SW1 for current or voltage (see Table 1).

2. Set position 1 through position 4 of input range switch “SW1” for the desired input range (see Table 1).

3. Set position 5 of input range switch “SW1" to ON for unipolar (e.g. zero based, 0-20mA) range or

OFF for bipolar (e.g. -100% offset, -20 to 20mA) range (see Figure 4).

4. Set position 6 and 7 of input range switch “SW1" to ON for a HI trip setpoint or OFF for a LO trip

setpoint (see Figure 4).

5. Set position 8 of input range switch “SW1" to ON for non-failsafe operation or OFF for failsafe

operation (e.g. alarm trips upon power failure).

1. After configuring the DIP switches, connect the input to a calibrated DC source and apply power. Refer

to the terminal wiring diagram.

Note: to maximize thermal stability final calibration should be performed in the operating installation,

allowing approximately 1 to 2 hours for warm up and thermal equilibrium of the system.

2. Setpoint: set deadband at its minimum (fully Counter Clockwise) before adjusting the setpoint. With the

desired trip voltage or current input applied, adjust setpoint until the relay trips. For HI trip calibration, start

with the setpoint above the desired trip. For LO trip calibration, start below the desired trip.

3. Deadband: Set deadband to its minimum (fully counter clockwise). Set the setpoint to desired trip.

Adjust voltage/current input until relay trips. Readjust deadband to 5% (fully Clockwise). Set

voltage/current input signal to desired deadband position. Slowly adjust deadband until relay untrips.

When switching inductive loads, maximum relay life and transient EMI suppression is achieved using external

protection (see Figures 2 and 3). Place all protection devices directly across the load and minimize all lead

lengths. For AC inductive loads, place a properly rated MOV across the load in parallel with a series RC

snubber. Use a 0.01 to 0.1

HF pulse film capacitor (foil polypropylene recommended) of sufficient voltage

and a 47

M, 1/2W carbon resistor. For DC inductive loads, place a diode across the load (PRV > DC supply,

1N4006 recommended) with (+) to cathode and (-) to anode (the RC snubber is an optional enhancement).

Configuration

WARNING:

Calibration

Relay Protection and EMI

Suppression

Figure 4

G108 Input range/

function selection

(SW1), factory

default settings